HXGN15-12 ring main unit is a fixed AC metal-enclosed MV switchgear for 12 kV ring-fed or radial systems. It combines SF6 load switch, load switch-fuse combination or vacuum breaker units to distribute, control and protect feeders and distribution transformers in compact urban and industrial substations.
Trade term: FOB / CIF. MOQ 20 pcs per model. Lead time 3–7 working days for standard models, 15–30 days for customized builds. Payment 50% T/T deposit, balance against copy of B/L.
| Standard | GB 3906, GB/T 11022, IEC 62271-200 |
|---|---|
| Rated voltage | 12 kV; rated frequency 50 Hz |
| Rated current | Main and busbar 630 A; fuse-combination unit limited by HV fuse (up to 125 A) |
| Short-time withstand | 20 kA / 3 s; 25 kA option |
| Peak withstand | 50 / 63 kA |
| Power frequency withstand | 1 min 42 kV phase-to-phase/earth; 48 kV across break |
| Lightning impulse withstand | 75 kV phase-to-phase/earth; 85 kV across break |
| Internal switch | SF6 load switch, load switch-fuse combination; vacuum breaker option |
| Protection | IP2X; metal-enclosed, fully insulated busbar option |
Values above are taken from the manufacturer datasheet for this series. The exact model, range and options are confirmed on the order confirmation, and a signed datasheet plus test report is supplied with the shipment.
Reference: GB 3906 / IEC 62271-200 metal-enclosed MV switchgear. Certificates are offered only where available for the selected model.